Меню
      Рус Анг
SAU GRS

SAU GRS

Automatic control system for gas-distribution station

ACS GDS is intended for the control and automation of one- or two-thread gas-distribution stations of different capacities.

MAIN TASKS TO BE SOLVED

  • Execution of automatic control programs in emergency situations.
  • Tap control
  • Ability to query gas flow rate calculators via interface, calculation of summary gas flow rate and control of gas odor system.
  • Data acquisition, processing and archiving.
  • Automatic transmission of emergency and warning signals to the workstation operator and the recording of each emergency event.
  • Change of warning and emergency setups from the built-in and remote operator workstation.
  • Control of exhaust ventilation, emergency light and acoustic signaling.
  • Good condition monitoring of all operating mechanisms of technological equipment, continuously runs self-diagnostics on all system modules and supply units.
  • Displays information about process flows and the state of equipment graphically via the remote operator workstation.
  • Integration with the protection signaling system.
  • Integration with the fire signaling system.
  • Interaction with remote control & monitoring system supporting the command transmission via communication line from the operator to control objects, and remote control devices in operator house.
  • Data transmission to information-control systems via interface lines, telephone lines or radio channel.
  • Provides uninterrupted electricity supply support of ACS GPA and automation devices in the event of voltage loss from an uninterrupted supply assembly with the use of a back up battery (from 2 to 8 hours).

SPECIFICATIONS

  • 24 analog input signals ТСМ (RTD Copper ), ТСП (RTD Platinum) thermal resistance transducers with calibrations under State Standart 6651; (0-5), (0-20), (4-20) mA direct current; direct voltage from ±15 mV to 550 V; alternating voltage from 200 mV to 600 V; frequency signals from (0-500) Hz to (0-100) kHz; including signals from ТСМ (RTD Copper), ТСП (RTD Platinum ) and pressure sensors with spark-proof input circuits of level “ia”.
  • 104 discrete low-voltage (24 V) input signals, including 24 differential and 5 groups with one common (of 16 signals “dry contact”).
  • Up to 16 low-frequency number-pulse (count) inputs with pulserecurrence frequency up to 100 Hz.
  • 32 output discrete signals (transistor with open collector = 30 V, 100 mA;
  • electromechanical relays with commutating contact (~220 V or = 30 V, 6 A) or optorelays (~220 V, 2 A or = 24 V, 2 A).
  • Up to 4 analog output signals (0-20), (4-20) mA or (0-10), (0-5) V.
  • Cycle of inquiry and control under discrete signals – 100 ms (under analog signals – 1 s).

INSTALLED EQUIPMENT SPECIFICATIONS

  • ACS GDS cabinet with built-in panel operator workstation: 2200 x 600 x 400 mm (H x W x D).
  • Remote operator workstation: industrial desktop computer: system unit, keyboard, mouse, acoustic columns – at client's request.
  • ABP1300-ОО-24/220 (ABP - Uninterruptible power supply) uninterrupted supply assembly - 440 x 530 x 500 mm (H x W x D) – at client's request.
  • 2 pieces of AKB DJM 12200 (12 V, 200 A*h) – 224 x 522 x 240 mm (H x W x D) – at client's request. (АКБ- storage battery)
  • ABP & AKB case-support – 300 x 540 x 500 mm (H x W x D) – at client's request.
Хотите узнать больше? Получите консультацию менеджера
Спасибо за Ваше обращение!

В ближайшее время мы с Вами свяжемся.